The friction head loss and the pressure drop of water in a pipe, by the Hazen-Williams formula: give the flow, the internal diameter, the length and the C-factor. Free, nothing to install, and nothing you type leaves your browser.
Water at 1000 kg/m³, g = 9.81 m/s². The calculation runs in your browser: nothing you type is sent anywhere.
The Hazen-Williams formula gives the friction head loss of water flowing full in a pipe. In SI units:
| Pipe | C |
|---|---|
| New steel | 120 |
| Used steel | 100 |
| Cement-lined ductile iron | 140 |
| PE or PVC | 150 |
A higher C is a smoother pipe and a smaller loss, and C falls as a pipe ages. Fire protection codes such as NFPA 13 give their own table, and the project specification has the last word: choose Custom to enter its value.
A valve on this line that can close fast? Check the surge with the water hammer calculator.
100 m³/h of water in a new steel line (C = 120) of 150 mm internal diameter and 500 m, rising 10 m from the inlet to the outlet. These are the calculator's starting values.
| Step | Calculation | Result |
|---|---|---|
| Flow | Q = 100 / 3600 | 0.02778 m³/s |
| Flow area | A = π × 0.150² / 4 | 0.01767 m² |
| Velocity | v = 0.02778 / 0.01767 | 1.57 m/s |
| Friction head loss | hf = 10.67 × 500 × 0.027781.852 / (1201.852 × 0.1504.87) | 10.15 m, 2.03 m per 100 m |
| Friction pressure drop | 1000 × 9.81 × 10.15 | 0.996 bar |
| Elevation | 1000 × 9.81 × 10 | 0.981 bar |
| Pressure drop | ΔP = 1000 × 9.81 × (10.15 + 10) | 1.98 bar = 197.7 kPa |
The line needs 1.98 bar more at its inlet than at its outlet: 0.996 bar for friction and 0.981 bar to lift the water 10 m. At 1.57 m/s the velocity is within the usual range for water.
The one your project specification gives. As a guide: about 120 for new steel, 100 for steel after years of service, 140 for cement-lined ductile iron and 150 for PE and PVC. Fire protection codes such as NFPA 13 have their own table, with 120 for black steel in wet systems and 100 in dry systems.
Yes. Hazen-Williams is the friction formula of fire water calculations to NFPA 13, 15 and 24. The codes write it with an exponent of 1.85 and their own units; the two forms agree within about 1 %. For the worked example the codes' SI form gives 0.993 bar of friction, against 0.996 bar here.
No, only the straight pipe. Add the equivalent length of each elbow, tee and valve to the pipe length, or model them with their K-factors.
Hazen-Williams is empirical: it was fitted to water at ordinary temperatures, and it keeps C fixed although the friction of a real pipe changes with the velocity and the diameter. Darcy-Weisbach with the Colebrook friction factor holds for any liquid and temperature. For water at usual velocities the two are close; for other fluids, hot water or very low or high velocities, use Darcy-Weisbach.