This is the shortest way from an empty sheet to a result. It has no example in it: it says what is pressed, in what order, and what the program answers. The training manual of the mode works through complete systems and explains every window; come back to this page for the order of things.
1 The window#

- The ribbon has the pages Home, Tools, Transient and Reports. File, at its left, holds New, Open, Save and Save As. New starts with the choice of the mode, Liquid or Gas, and opens the sheet.
- The Equipment strip holds everything that is placed on the sheet. Rest the mouse on a square to see its name. The surge protection - relief valve, air valve, accumulator, surge tank - and the controllers are greyed until the Transient mode is on.
- The panel at the right has two pages: Properties, the inputs and results of the element that is selected, and Elements, every element of the model with a box to find one by name.
- The status bar says where the model stands: Missing inputs, Ready to run, Solved, or Solved with warnings or errors. Click it for the list.
A model is links joined at nodes. A link carries flow: a pipe, a pump, a valve, a fixed loss (PD), a tank, a nozzle. A node is where links meet and where a pressure is reported.
2 A transient in seven steps#
The Transient mode starts from the steady state of the same model and follows what happens when something changes: a valve moves, a pump stops. Build the model and solve its steady state first (the Liquid quick start).

- Switch to the Transient mode. On the Transient page move Transient Mode to on and confirm. A window lists what the mode needs of the model. The commands of the page then show, and all of them open one window, Transient, at one of its six tabs. A node of flow is enough for the run's edges: a pressure is no longer required.
- Give what a transient needs. Each property window now has a Transient page. A pipe: its outside diameter and material, from which its wave speed is worked out. A pump: its Modelling - Simple, Inertia or Four quadrant - with its moment of inertia and rated speed. A valve: its characteristic; a check valve is a valve with No reverse flow ticked. A tank: whether its level is held or varies in the run.
- Setting. Wave speed Calculated Per Pipe (or one value typed for all pipes), and the pipe restraint. Leave Cavitation model at None for a first run. Tick Enable Dry pipe selection only for pipes that start empty.
- Integrator (Figure 3). The initialisation time, the end time, the time step and the output step. The table at the right shows how each pipe is resolved at that step: its reaches and the error in its wave speed. Shorten the step, or declare a pipe short, until no pipe that matters shows a large error.
- Controllers. Nothing moves unless a controller moves it. Press Add controller, press Select OP and choose the opening of a valve, the speed of a pump, or a pump itself. Manual is a schedule, time against value; for a pump it is a list of Trip and Start events. Automatic holds a pressure, a flow or a level at its set point with a gain and an integral time.
- Charts. Press Add chart, then Set variables, and choose what to follow; Limit line draws a design pressure on the chart. Only what is asked for is kept as a history. Add transient chart, on the menu of an element, starts one from the sheet.
- Run, on the Transient page. Read the charts (Figure 4): the table under each gives the highest and lowest value of every series and when. On the sheet the label selectors now offer Max Pressure and Min Pressure, the envelope of the run. Read the message at the end of the run, if there is one.


| Where | What it is for |
|---|---|
| Forces | The unbalanced force on a straight run of pipe between two cuts, for the pipe supports: its maximum, its minimum and its history |
| Scenarios | Cases - the same model with a controller or a boundary changed - run one after the other, judged against limits and written into a report |
| Setting, Cavitation model | DVCM or DGCM, when a pressure of the first run reaches the vapour pressure: the liquid parts there, and the run without a model is no longer a result |
| Setting, Unsteady friction | Damps the later cycles of a wave as a real line does; the first peak does not change |
| Equipment strip | Surge relief valve, air valve, accumulator and surge tank: the protection, drawn like any other element, enabled in the Transient mode |
3 Before a result is used#
- The steady state says Solved with no error in its list.
- The lowest pressure of a transient is above the vapour pressure. If it is not, turn a cavitation model on and run again; compare DVCM with DGCM.
- The Integrator's table shows no pipe that matters with a large wave speed error. Run once more at half the time step: the peaks should move little.
- A pressure made by a cavity or an air pocket that closes is an order of magnitude, not a number to three figures.
- A relief valve relieves to a pressure: give its outlet node 0 barg, or a line. An air valve has one connection and always opens to the atmosphere.
- A pump that stands by is entered with Pump on No; a valve that is shut is entered at 0 %. The Transient mode works with constant properties.
Next: the Transient Training Manual, ten examples, each with its project file.